Roofing Code: Chapter 15
Roofs and Roof Structures
Section 1507.12, Thermoset Single-Ply Roofing:
The installation of thermoset single-ply roofing shall comply with the provisions of this section.
1507.12.1, Slope. Thermoset single-ply membrane roofs shall have a design slope of a minimum 1/4 unit vertical in 12 units horizontal (2 percent slope) for drainage.
1507.12.2, Material standards. Thermoset single-ply roof coverings shall comply with ASTM D 4637, ASTM D 5019 or CGSB 37-GP-52M.
Code Interpretation:
Thermoset roof classifications include rubber polymer sheets such as EPDM and butyl rubber. This section implies that thermoset roof systems shall be applied on roof substrates that have a minimum slope of 2 percent (1/4 inch in 12 inches). Proper roofing industry standards require that the slope of the deck shall be sufficient to remove all standing water from the roof system a maximum of 48 hours after a rainfall. The roof deck slope must comply with IBC requirements (1/4 inch in 12 inches). If this slope is not adequate to remove all standing water from the system, artificial means (such as tapered insulation) may be required.
The section also implies that the thermoset materials must meet the requirements set forth by ASTM (American) or CGSB (Canadian) standards for physical property testing. Physical property tests typically include moisture resistance, tensile, elongation, mil thickness, accelerated weathering and wind uplift testing.